Where to start
- Record hot-water inlet and cold-water outlet temperatures, entering-air wet bulb at representative air inlets, circulating flow and fan/cell status in the same stable period. Note RPM or speed command and any operating changes.
- Calculate Range (hot inlet minus cold outlet) and Approach (cold outlet minus entering wet bulb). A higher wet bulb can explain warmer outlet water even when Approach is similar. Compare at similar heat load, flow and fan operation.
- If Approach rises under comparable conditions, inspect nozzle distribution, fill deposits, air bypass and fan operation. Uneven water distribution or poor air intake can justify corrective work before fill replacement is scoped.
Illustrative calculation: 100 m³/h, 37/32 °C water and 27 °C entering wet bulb give Range 5 °C, Approach 5 °C and approximately 582 kW of heat rejection. Formal acceptance testing follows the applicable CTI test code and program requirements.