FAN ENERGY

Higher-IE motor, VFD or EC fan. Where should you start?

Start with the fan you already have. Check how much cooling the site needs and how much power the fan uses at the speeds it actually runs.

Back to articles

Where to start

  1. Log supply-side input kW, RPM, run hours and water outlet temperature. For a fan-system comparison, establish the airflow and pressure at comparable points and record circulating flow, load and entering wet bulb.
  2. For a motor-only replacement, hold shaft duty constant. Use supplier efficiency at that load. A nameplate full-load value can be used as a stated assumption when part-load data is unavailable.
  3. For AC with VFD or an EC assembly, request fan curves and supply-side power for the required airflow and pressure. Include drive or controller losses and confirm fit, environment, serviceability and outlet temperature at comparable conditions.

Estimate annual energy from measured or supplier-supported input kW and hours at each operating point. Label the source and conditions before quoting savings.

Primary references